PRUDUCT
-
LOCATION:Gas alarm controller
-
Gas alarm controller
AS-3100 Combustible gas alarm controller
Product features
★Standard DC (4 ~ 20) mA signal input,versatility;
★Wall-mounted installation is simple and easy to operate;
★Industrial use of the LCD screen, all Chinese display interface having a cylindrical concentration;
★Black box function, storing 1000 data;
★The CPU adopts high-grade single-chip microcomputer, which has fast running speed and high precision;
★With RS485 communication interface and DC4~20ma output function;
★Zero and calibration of its displayed values;
★With fault alarm output contact, low limit alarm output contact, high limit alarm output contact and sound and light alarm output contact four sets of output contacts.
Technical Parameters
♦Installation method:Wall-mounted
♦Display mode:LCD
♦Measuring range:0~100%LEL,0~1000×10-6(Full range adjustable),0~35%VOL(Full range adjustable)
♦Display accuracy:≤±1%F.S
♦Alarm mode:Sound and light alarm
♦Control quantity:1 detector
♦Receiving signal:DC(4~20)mA current signal
♦Fault signal:≤2mA
♦Alarm settings: Low limit alarm :adjustable(the factory default 25% of full scale) High limit alarm :adjustable(the factory default 50% of full scale)
♦ Output Voltage:DC 24V±10%
♦Record alarm information:Can store 1000 pieces of information,the oldest record automatically cleared after 1000
♦Communication interface:RS-485
♦Operating voltage:Automatic switching of mains and backup power (backup power is optional)
Main power:AC 187V~242V
Backup power:1.3AH/12V、1 knot
♦Power consumption:<3W
♦Output control:With low and high concentration alarm output contacts, sound and light alarm output contacts and fault alarm output contacts(Capacity:3A/220VAC、3A/30V)
♦Transmission distance:1.5km(Loop resistance<20Ω)
♦Ambient Temperature:(0~+40)℃
♦Relative Humidity:(10~95) %RH
♦Pressure Range:(86~106) kPa
Shape and installation dimensions
Terminal block description