PRUDUCT

  • LOCATION:Fixed gas detector

  • Fixed gas detector

GT-AS1000b Industrial and commercial flammable gas detector

GT-AS1000b Industrial and commercial flammable gas detector



Technical Parameters

 

★ Display method:  OLED

★ Detection gas:  Combustible gas

★ Detection principle: Catalytic combustion

★ Detection range:  3~100%LEL

★ Accuracy:  ±2% F.S

★ Sample method: Free diffusion type

★ Response time: T90≤30s

★ Operating voltage:  DC 24V±15%

★ Working current:     80mA / 150 mA  (with Sound and light alarm)

★ Maximum consumption: 2W/  3.6W (with sound and light alarm)

★ Output signal 1: DC 420mA

★ Output signal 2: Modular plug-wayStandard 485 signal RTU format (Optional)

★ Output signal 3: Modular plug-wayImplement bus signal outputUsed with AS2000A controllerOptional

★ Built-in relay :  A set of multi-function contact outputsDC30V/2A),Can be selected as normally open, normally closed, passive, active, low-range action or high-range action.

★ Alarm set value:  Adjustable Factory default 25%LEL50%LEL

★ Sound intensity:  85dB /1 meter (Sound and light alarm)

★ Case Material:  Aluminum alloyExternal Metal baking varnish

★ Wiring system: hree-wire systemDC 420mA)、Four-wire system(Bus output formOptional bus conversion module)

★ Explosion proof electrical interface: M20*1.5(Acousto-optic interfaces3/4NPT(F)Electrical Interface

★ Explosion-proof grade:  Ex dCT6 Gb

★ Explosion-proof sound and light alarm:  Optional

★ Protection classification: IP66

★ Weight: 1.3kg

★ Transmission distance: 1.5kmLoop resistance20Ω)

★ Ambient temperature: (-40~+70)℃

★ Relative humidity: (1095)%RHNo condensation

★ Pressure range: (86106)kPa

★ Executive standard: GB15322.1-2003,GB3836.1-2010,GB3836.2-2010,GB50493-2009  


Product features

 

♦ Imported catalytic combustion sensor

♦ Modular design of the whole machine according to SIL requirements

♦ With ABS circuit board protection device

♦ The sensor adopts a plug-in structure

♦ Good anti-poisoning performance, anti-interference ability

♦ Full-featured field-free opening operationmagnetic bar adjustment

♦ Wide voltage supply, anti-reverse protection, short circuit protection and output current protection

♦ A set of multi-function relay output is adjusted freelyActive, passive, normally open, normally closed, high limit action or low limit action

♦ Standard 485 signal RTU format   Optional);

♦ Modular installationadapt to a variety of different ways of mounting

♦ Optional accessories, multi-line output to bus output

♦ Can be equipped with live sound and light alarmShow eye-catchingThe lampshade is made of high molecular polymer materialStrong impact resistanceWith three different sound and light tipsFault, low segment alarm, high segment alarm)。


Explosion environment - Flame-proof connection mode of cable incoming wire  


◣ Internal terminal wiring : All lead-in wires are stripped 5mm and directly connected or connected to u-terminal after tin plating.

◣ Threading requirements : Separate into metal pipe (galvanized pipe) ,Do not enter the same tube with power line, lighting line and ac line.

◣ Cable: Use control cable such as KW-3×x1.5,or watertight cable such as JHS-3×1.5 (depends on the environment)

◣ Joint processingAll joints should be pressed and sealed with insulation sleeve to prevent short circuit, leakage and water immersion to meet the requirement of flameproof。 



Dimensions




Component diagram






 


Installation drawing