PRUDUCT
-
LOCATION:Fixed gas detector
-
Fixed gas detector
GT-AS1000I Combustible gas detector for industrial and commercial use
GT-AS1000I Combustible gas detector for industrial and commercial use
Property
★ Display method: No display
★ Detection gas: Combustible gas
★ Detection principle: Catalytic combustion
★ Detection range: (3~100)%LEL
★ Accuracy: ±3% F.S
★ Response time: T90≤30s
★ Recovery time: ≤30s
★ Sample method:Free diffusion type
Electrical specification
★ Working voltage:DC24V±15%
★ Working current:≤50mA / ≤150mA(with Sound and light alarm)
★ Maximum consumption:≤1.3W / ≤3.9W(with Sound and light alarm)
★ Wiring system: Three-wire system
★ Alarm set value:Adjustable Low alarm25%LEL、High alarm50%LEL
★ Output signal: DC(4~20)mA
A set of switch measuring contacts (1A/125VAC、2A/24VDC),Normally open 、normally closed、 passive and active can be set (Optional)
Structural property
★ Case Material: Aluminum alloy,External Metal baking varnish
★ Explosion proof electrical interface: M20X1.5
★ Weight: 0.65kg / 0.80kg(with Sound and light alarm)
Certification
★ Protection classification:IP65
★ Explosion-proof grade: Exd ⅡC T6 Gb
Operating environment
★ Ambient temperature: (-40~+70)℃
★ Relative humidity: (10~95)%RH (No condensation)
★ Pressure range: (86~106)kPa
★ Transmission distance: 1.5km(Loop resistance<20Ω)
★ Executive standard:GB15322.1-2003,GB3836.1-2010,GB3836.2-2010
Component diagram